Reactor Safety Area
Unplanned Reactor Scram(URS)
The URS indicator is the number of unplanned reactor scrams during possible critical hours per actual critical hours.
Note : All the automatic and manual scrams prescribed in the reporting criteria are included.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Evaluated Value | < 3 | |
Good | ![]() |
6 ≤ | Evaluated Value | < 6 |
Normal | ![]() |
6 ≤ | Evaluated Value | < 20 |
Warning | ![]() |
20 ≤ | Evaluated Value |
Unplanned Power Reduction(UPR)
UPR indicator is the number of unplanned power reduction by more than 30% during possible critical hours per actual critical hours.
Note : Power reductions requested by the load dispatcher, and unplanned power changes caused by the external event such as typhoon, or the transient of the off-site transmission line are not included.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Evaluated Value | < 6 | |
Good | ![]() |
6 ≤ | Evaluated Value | < 12 |
Normal | ![]() |
12 ≤ | Evaluated Value | < 20 |
Warning | ![]() |
20 ≤ | Evaluated Value |
Unplanned Reactor Scram with Complications(USwC)
USwC indicator is the number of unplanned reactor scrams with complications during possible critical hours.
Note: This indicator is a subset of the URS indicator and the scram considered in this indicator must have counted in the URS indicator.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Evaluated Value | ≤ 1 | |
Good | ![]() |
1 < | Evaluated Value | |
Normal | ![]() |
Evaluated Value | ||
Warning | ![]() |
Evaluated Value |
Safety Injection System Unavailability(SI)
SI indicator is the fraction of unavailable hours against the hours that SI system is required.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Boundary Value | < 0.015 | |
Good | ![]() |
0.015 ≤ | Boundary Value | < 0.05 |
Normal | ![]() |
0.05 ≤ | Boundary Value | < 0.1 |
Warning | ![]() |
0.1 ≤ | Boundary Value |
Emergency Diesel Generator System Unavailability(EDG)
EDG indicator is the fraction of unavailable hours against the hours that EDG system is required.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Evaluated Value | < 0.025 | |
Good | ![]() |
0.025 ≤ | Evaluated Value | < 0.05 |
Normal | ![]() |
0.05 ≤ | Evaluated Value | < 0.1 |
Warning | ![]() |
0.1 ≤ | Evaluated Value |
Auxiliary Feedwater System Unavailability(AFW)
AFW indicator is the fraction of unavailable hours against the hours that AFW system is required.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Boundary Value | < 0.015 | |
Good | ![]() |
0.015 ≤ | Boundary Value | < 0.05 |
Normal | ![]() |
0.05 ≤ | Boundary Value | < 0.1 |
Warning | ![]() |
0.1 ≤ | Boundary Value |
Residual Heat Removal System Unavailability(RHR)
RHR indicator is the fraction of unavailable hours against the hours that RHR system is required.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Boundary Value | < 0.015 | |
Good | ![]() |
0.015 ≤ | Boundary Value | < 0.05 |
Normal | ![]() |
0.05 ≤ | Boundary Value | < 0.1 |
Warning | ![]() |
0.1 ≤ | Boundary Value |
Cooling Water System Unavailability(CW)
CW indicator is the fraction of unavailable hours against the hours that CW system is required.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Boundary Value | < 0.015 | |
Good | ![]() |
0.015 ≤ | Boundary Value | < 0.05 |
Normal | ![]() |
0.05 ≤ | Boundary Value | < 0.1 |
Warning | ![]() |
0.1 ≤ | Boundary Value |
Safety System Functional Failures(SSFF)
SSFF indicator is the number of events or conditions that prevented, or could have prevented the fulfillment of the safety function.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Boundary Value | ≤ 5 | |
Good | ![]() |
5 < | Boundary Value | |
Normal | ![]() |
Boundary Value | ||
Warning | ![]() |
Boundary Value |
Fuel Reliability(FR)
FR indicator is the percentage of the maximum value of I-131 in the RCS to the limit value of Technical Specification.
Note : Maximum value over a month during the evaluating period, for each quarter will be used for the calculation of indicator value
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Evaluated Value | < 50% of limit value | |
Good | ![]() |
50% of limit value ≤ | Evaluated Value | < 70% of limit value |
Normal | ![]() |
70% of limit value ≤ | Evaluated Value | < 100% of limit value |
Warning | ![]() |
100% of limit value ≤ | Evaluated Value |
Reactor Coolant Leakage(RCL)
RCL indicator is the percentage of the maximum RCS leakage rate to the limit value of Technical Specification.
Note : Maximum value used for the calculation includes both the identified and unidentified leakage.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
Evaluated Value | < 50% of limit value | |
Good | ![]() |
50% of limit value ≤ | Evaluated Value | < 70% of limit value |
Normal | ![]() |
70% of limit value ≤ | Evaluated Value | < 100% of limit value |
Warning | ![]() |
100% of limit value ≤ | Evaluated Value |
Containment Reliability(CR)
CR indicator is the combination of ILRT results and LLRT results.
Note : Criteria of ILRT(Integrated Leak Rate Test) results and LLRT(Local Leak Rate Test) results are based on the La of the plant Technical Specification.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
90% ≤ | Evaluated Value | |
Good | ![]() |
80% ≤ | Evaluated Value | < 90% |
Normal | ![]() |
60% ≤ | Evaluated Value | < 80% |
Warning | ![]() |
Evaluated Value | < 60% |
Emergency Preparedness(EP)
EP indicator is the combination of Emergency exercise, Training of emergency personnel and emergency facility plus Response capability(only when the Radiation Alert is declared).
Note : This indicator is evaluated based on the data over the previous three years. Response capability is evaluated with respect to the degree of the EOP observance.
Boundary Value
Grade | Color | Boundary Value | ||
---|---|---|---|---|
Excellent | ![]() |
90% ≤ | Evaluated Value | |
Good | ![]() |
80% ≤ | Evaluated Value | < 90% |
Normal | ![]() |
60% ≤ | Evaluated Value | < 80% |
Warning | ![]() |
Evaluated Value | < 60% |